How many Popups can be opened with Vijeo Designer V6.2?
Issue
What is the total amount of Popup screens that can be opened at one time in Vijeo Designer v6.2 Runtime?
Product Line
Vijeo Designer Runtime v6.2
Environment
Simulated or Physical Human Machine Interfaces (HMI)
Resolution
Up to 3 popup screens can be opened simultaneously with Vijeo Designer.
The keypad that appears when you touch a Numeric or String Display counts as one popup.
Requirement 1: The Popup Panel must be configured in a different windows.
In this example, Popup Panel 2 and 3 cannot be on the screen simultaneously because they are part of the "1: Window1" group.
However, since Panel 5 is in a separate window group "2: Window2", that means that:
a) Popup Panel 5 and Panel 2 can simultaneously be on the screen.
b) Popup Panel 5 and Panel 3 can simultaneously be on the screen.
Requirement 2: Persistent mode must be selected from the Property Inspector for all your Window Groups.
(Persistent Mode keeps the Popup displayed even if you change Base Panels on the HMI Runtime)
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Опубликовано для: Schneider Electric Казахстан
Вложения
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.