What is CVT calibration data?
Issue
User wants to know what CVT calibration data is.
Product
N, U, W, RL Series Reclosers
Environment
WSOS5
Cause
Voltage measurement accuracy in these recloser systems depends on device‑specific calibration values determined during factory testing.
Resolution
CVT calibration data is one of the key variables used by the voltage‑measurement algorithm in the recloser control system. These data values are:
- Determined during final routine factory tests.
- Stored in the SCEM board for the N, U, W, and RL series reclosers.
- Stored inside the ADVC3 controller for E‑series devices (paired during factory CVT calibration).
Because of natural manufacturing tolerances in electronic components and bushings, each bushing and SCEM combination has unique CVT calibration data.
Impact of SCEM Replacement
For N, U, W, and RL series reclosers, replacing the SCEM board may cause incorrect voltage readings.
To correct this:
- Reload the latest CVT calibration data file into the device.
- Use the Calibration menu in WSOS5 to fine‑tune voltage measurement.
- Follow the on‑site CVT Calibration procedure for detailed steps.
Proper loading and calibration ensure accurate voltage measurement after hardware replacement.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.