Video: How to generate a Meter Configuration report using ION Setup

Issue
User may need to generate a Meter Configuration report or Event Log in ION Setup

Product Line
PowerLogic Power Meters
ION Power Meter

Environment

ION Setup

Resolution
For ION Meters:

  1. Select the desired ION Meter
  2. Double-click on Setup Assistant to launch Setup Assistant
  3. Select Reports
  4. To generate a Meter Configuration report, double-click on Meter Configuration
    • To save the file in text format, click Save As...
    • ​Select a file location, type desired file name, and click Save



For PowerLogic Meters

  1. Select the desired PowerLogic Meter
  2. Double-click on Reports
  3. To generate a Meter Configuration report, select Meter Configuration and then click Display
    • To save the file in text format, click Save As...
    • ​Select a file location, type desired file name, and click Save