VW3A1111 Graphic Display terminal can be used for Drives RESET regardless of the Control Channel used, but it needs to be enabled.
This parameter is present in the menu:
5.5 Command and Reference
Stop key Enable (PST parameter) YES (by default)
Now press enter on this parameter, and you will see:
The values: no - yes - all.
When all is selected, the drive can be reset regardless of control channel.
This parameter is present in the menu:
5.5 Command and Reference
Stop key Enable (PST parameter) YES (by default)
Now press enter on this parameter, and you will see:
The values: no - yes - all.
When all is selected, the drive can be reset regardless of control channel.