Чем мы можем помочь сегодня?
PM5000 Digital Output Behaviour Modes
Issue
User would like to know the differences between the Digital Output Behaviour Modes "Normal", "Timed", and "Trip Coil"
Product Line
PM5300
PM5500
Environment
Front panel or ION Setup
Resolution
Descriptions of the three (3) digital output behaviour modes are below.
Normal:
User would like to know the differences between the Digital Output Behaviour Modes "Normal", "Timed", and "Trip Coil"
Product Line
PM5300
PM5500
Environment
Front panel or ION Setup
Resolution
Descriptions of the three (3) digital output behaviour modes are below.
Normal:
- Digital output will turn ON when the specified external or alarm condition is met as defined in Control Mode
- The digital output remains ON only while the alarm is active
- Digital output will turn ON when the specified external, demand sync, alarm, or energy condition is met as defined in Control Mode
- The digital output remains ON for the time period (in seconds) defined in the "On Time" setup parameter
- Digital output will turn ON when the specified external or alarm condition is met as defined in Control Mode
- The digital output remains ON until the command number 6004 is sent to the meter from a PLC or PC.
- Please check the command structure in the Modbus register list at PowerLogic PM5000 Series (PM5100, PM5300, PM5500) Modbus Register List
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.