Issue:
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.