What can cause an ASF or angle error on the ATV630 and ATV930 Process drives?
Issue:
Posible cause for an ASF or angle error on the ATV630/930 drives.
Product Line:
ATV630 and ATV930 Process drives
Environment:
All
Cause:
For synchronous motors , the wrong speed loop setting when the reference goes to zero.
Resolution:
Verify the speed loop parameters
Verify the motor phases and the maximum current allowed by the drive.