What can cause a CFF fault on the ATV630 and ATV930 Process drives?
Issue:
Cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.
Resolution:
At power on the hardware configuration is approved, if option card,
bower board has changed this error occurs.
Probable cause:
Option card removed, power board changed and not rated.
Use SoMove service section to identify the cause of the CFF.
Remedies:
- check all option cards if they are connected correctly.
- check if the power board / control block fit's to the drive.
- If the option card was removed intended, a factory setting needs to be performed
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:Support | Schneider Electric Global (se.com)
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.