Issue:
Undervoltage alarm on an ATV212
Product Line:
Altivar 212
Environment:
All
Cause:
The input voltage is too low
Resolution:
Check the input voltage and rectify any issues
Select the correct setting for F627
Enable catch on the fly, parameter F301
Set F302 to 2