How to set up ATV630 for profibus communication?
Issue:
Setting up ATV630 for profibus communication.
Product Line:
Altivar 630
Environment:
All
Cause:
Setup
Resolution:
1) Set profibus address - [Communication] / [Comm Parameters] / [Profibus]
(PbC-)
2) Set reference frequency to communication module - [Complete settings] / [Command and Reference] / [Ref Freq 1 Config]
That is is all on drive side, all others has to be configured in the PLC.