1/ Use the Unity Loader utility.
2/ Connect the PC that is running the Unity Loader to the Ethernet communications module.
3/ Launch the Unity Loader.
4/ Click the <Firmware> tab.
5/ In the PC list box, select the .ldx firmware file.
6/ When connected with Ethernet, check that the MAC address indicated in the PLC box
corresponds to the MAC address marked on the connected Ethernet device.
7/ Check that the transfer sign is green allowing transfer from the PC to the Ethernet module.
8/ Click on <Transfer>.
9/ Click on <Close> when transfer is complete.
NOTE: Make sure that the firmware update security is set to allow firmware updates.
-----------
The Unity Pro DTM provides security services to the BMENOC0301/11 Ethernet communication module.
Enable and disable these services on the Security tab in the Unity Pro DTM.
a/ Open the Unity Pro DTM Browser in the Unity Pro M580 project.
b/ In the DTM Browser, double click on the BMENOC0301/11 module.
c/ Select <Security>
d/ Enable or disable (default) these items.
Firmware upgrade
Device configuration management using the FDR service
2/ Connect the PC that is running the Unity Loader to the Ethernet communications module.
3/ Launch the Unity Loader.
4/ Click the <Firmware> tab.
5/ In the PC list box, select the .ldx firmware file.
6/ When connected with Ethernet, check that the MAC address indicated in the PLC box
corresponds to the MAC address marked on the connected Ethernet device.
7/ Check that the transfer sign is green allowing transfer from the PC to the Ethernet module.
8/ Click on <Transfer>.
9/ Click on <Close> when transfer is complete.
NOTE: Make sure that the firmware update security is set to allow firmware updates.
-----------
The Unity Pro DTM provides security services to the BMENOC0301/11 Ethernet communication module.
Enable and disable these services on the Security tab in the Unity Pro DTM.
a/ Open the Unity Pro DTM Browser in the Unity Pro M580 project.
b/ In the DTM Browser, double click on the BMENOC0301/11 module.
c/ Select <Security>
d/ Enable or disable (default) these items.
Firmware upgrade
Device configuration management using the FDR service
Опубликовано для: Schneider Electric Казахстан