Issue:
Tesys T unit with LTMCUF keypad shows F09 fault code when powered. Customer is not using the FDR function.
Product line:
Tesys T, LTMR, LTMCUF
Environment:
Tesys T systems equipped with LTMCUF remote keypad.
Cause:
On initial power a backup function must be performed to backup a copy of the program to the LTMCUF keypad.
Resolution:
To initiate a backup function, press and hold the 2 round buttons with green circles around them for 3-4 seconds. This will initiate a backup function and save a copy of the current program on the Tesys T into the keypad. After this has completed, cycle power on the LTMR and it should boot without the F09 fault code.
Tesys T unit with LTMCUF keypad shows F09 fault code when powered. Customer is not using the FDR function.
Product line:
Tesys T, LTMR, LTMCUF
Environment:
Tesys T systems equipped with LTMCUF remote keypad.
Cause:
On initial power a backup function must be performed to backup a copy of the program to the LTMCUF keypad.
Resolution:
To initiate a backup function, press and hold the 2 round buttons with green circles around them for 3-4 seconds. This will initiate a backup function and save a copy of the current program on the Tesys T into the keypad. After this has completed, cycle power on the LTMR and it should boot without the F09 fault code.
Опубликовано для: Schneider Electric Казахстан


Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.