What could cause the Current Limitation function of the ATV71 series drive to not limit the motor current?
Issue:
Why would the Current Limitation function of the ATV71 series drive not limit running motor current.

Product Line:
ATV71 series drives.

Environment:
All

Cause:
Current Limitation has not been configured for the motor

Resolution:
When Current Limitation (CLI) is set to a value lower than the no-load current of the motor, the function becomes inactive.  Otherwise there would be no way to turn the motor.   Ensure that the Motor Rated Current and Motor Thermal Current settings were configured to match the motor's nameplate.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

  • Инструмент для подбора продукции

    Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

  • Получить коммерческое предложение

    Заполните заявку онлайн, и с вами свяжется наш эксперт.

  • Где купить?

    Легко находите ближайшего к вам дистрибьютора Schneider Electric.

  • Центр поддержки

    Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings