Can I use a Vijeo Designer recipe object from the Webgate ?
Issue:
There are certain limitations while using Recipe objects in Web Gate.
Product Line:
XBTGT
HMIGTO
HMIGTU
IPC with VJD Runtime
Resolution:
The Data Sharing for the recipe control variable (_RecipeControlDefault) must be set to None.
Also the Internal Recipe variables associated to the ingredients must be set to none.
The external Recipe variables associated to the ingredients can be set to Read/Write.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.