Firmware Links for 140CPU43412A Update from Concept to Unity System
Issue:
Firmware Links for 140CPU43412A Update from Concept to Unity System
Product Line:
140CPU43412A , Concept, Unity Pro, Control Expert
Resolution:
To update your 140CPU43412A from Concept to Unity, first of all, please make sure the PV version is greater or equal to 04(PV can be seen from the top front of the CPU module), otherwise, it is not possible to update.
If you have the PV greater or equal to 04 but less then 16, please use the following intermediate OS and the last firmware:
140CPU43412U Intermediate OS (PV of module less than 16)
Quantum 140CPU43412U PV<16 Last Firmware
If you have the PV greater or equal to 16, please use the following intermediate OS and last firmware:
140CPU43412U Intermediate OS ( PV of module greater than or equal to 16 )
Quantum 140CPU43412U PV>=16 Last Firmware
Also, using Modbus communication for the firmware update is slow; Modbus plus is much faster. If you don't have the MB+ cable, another option is to send the part to our repair center for them to update the firmware for you.
For the Modbus communication cable, if you need to make a cable by yourself, please refer to attached pin out for details.
Please refer to the following link for the update procedure:
https://www.se.com/ww/en/download/document/EIO0000000064/
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Опубликовано для: Schneider Electric Казахстан
Вложения
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.