Чем мы можем помочь сегодня?

EBO SNVT types of third party devices doesnt match with SNVT types in TAC Vsta

EBO system processes data from third-party LonWorks devices according to the definition by Device Template, which is imported to a Building Operation Server (ES/AS-P).

In case SNVT types visible in EBO don't match with SNVTs in the TAC Vista database after the conversion procedure is done, there must be a discrepancy in XIF files that have been imported in advance.

Check the Network Variable index numbers for particular SNVTs that do not match after conversion against XIF files.

Make XIF file correction manually, following the LonMark org Technical Resource guide
chrome-extension://efaidnbmnnnibpcajpcglclefindmkaj/https://www.lonmark.org/wp-content/uploads/2020/12/LmXif4501.pdf

Schneider Electric Казахстан

Узнайте больше

Изделие:

Узнайте больше

Изделие:

Нужна помощь?

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.