How to properly calibrate the touchscreen on a HMIBMU series

Issue:
The touch screen calibration is still inaccurate even after using the Windows Control panel's Tablet PC Settings.

Product Line:
Magelis iPC, HMIBMU, HMIBMI

Resolution:
When calibrating the touchscreen of an HMIBMU or HMIBMI series, ensure not to use the Windows calibration tool. Instead, look for the PenMount Control Panel and use the calibration tool of that application. It provides the option for 25 points of calibration. By using 25 points, it gives the touchscreen a more accurate calibration.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.