Чем мы можем помочь сегодня?
PME 8.x/9.0 - Power Quality Report ITIC Curve update
Issue
The ITIC Curve in the Power Quality reports has been drawn wrong.
Product Line
Power Monitoring Expert 8.x, 9.0 (CU1 and CU2)
Environment
Power Quality Report
Cause
The actual PQ Events are located in the correct spots but the ITIC curve that is used as an overlay is incorrect.
Resolution
To correct this you can run the following script on the ApplicationModules database:
The ITIC Curve in the Power Quality reports has been drawn wrong.
Product Line
Power Monitoring Expert 8.x, 9.0 (CU1 and CU2)
Environment
Power Quality Report
Cause
The actual PQ Events are located in the correct spots but the ITIC curve that is used as an overlay is incorrect.
Resolution
To correct this you can run the following script on the ApplicationModules database:
UPDATE [ApplicationModules].[Configuration].[ConfigurationSettings] SET Value = '[{"X":0,"Y":0},{"X":0.02,"Y":0},{"X":0.02,"Y":70},{"X":0.5,"Y":70},{"X":0.5,"Y":80},{"X":10,"Y":80},{"X":10,"Y":90},{"X":2000,"Y":90}]'
WHERE ItemType = 'PowerQuality' AND Item = 'Curves' AND [Key] = 'IticLowPoints' AND UserId IS NULL
** see attachment containing the SQL script text
Опубликовано для: Schneider Electric Казахстан
Вложения
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.