- Issue
The operation successful bit of PIDFF block
will go to 0 and freeze when switch the mode of PIDFF block from Manual Mode to Auto Mode. - Product Line
M580 - Environment
Control Expert V14.0, Windows 10 64Bit - Resolution
Slow down the frequency of the enable bit of PIDFF block, then the issue will not occur. Опубликовано для: Schneider Electric Казахстан