Issue:
Can't access more than the Conf, SET, and SUP menus on the ATS22.
Product Line:
Altistart 22
Environment:
All
Cause:
Programming
Resolution:
This is an access level issue. Set LAC= On (Conf menu), and you will have access to all programming menus.

Can't access more than the Conf, SET, and SUP menus on the ATS22.
Product Line:
Altistart 22
Environment:
All
Cause:
Programming
Resolution:
This is an access level issue. Set LAC= On (Conf menu), and you will have access to all programming menus.
Опубликовано для: Schneider Electric Казахстан

