What size are the cable ports on the NetShelter CX, and how many are there?
Issue:
Cables need to enter and exit the cabinet.
Product Line:
NetShelter CX2
Environment:
All versions and serial ranges.
Cause:
Knowing the dimension of the cable port allows a person to calculate how many cables can fit through the opening.
Resolution:
AR4000MV: two ports, 30mm x 95mm at the botton and 26mm x 68mm at the top.
AR4018A/AR4018IA: one port, 350mm x 120mm at the bottom.
AR4024A/AR4024IA: one port, 350mm x 120mm at the bottom.
AR4038A/AR4038IA: two ports, 350mm x 120mm, one at the top and one at the bottom.
Cables need to enter and exit the cabinet.
Product Line:
NetShelter CX2
Environment:
All versions and serial ranges.
Cause:
Knowing the dimension of the cable port allows a person to calculate how many cables can fit through the opening.
Resolution:
AR4000MV: two ports, 30mm x 95mm at the botton and 26mm x 68mm at the top.
AR4018A/AR4018IA: one port, 350mm x 120mm at the bottom.
AR4024A/AR4024IA: one port, 350mm x 120mm at the bottom.
AR4038A/AR4038IA: two ports, 350mm x 120mm, one at the top and one at the bottom.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.