Why is my EcoStruxure Control Expert project opening in Read-only mode ?
Issue:
EcoStruxure Control Expert project opening in Read-only mode


Product Line:
EcoStruxure Control Expert, Unity Pro


Resolution:
When opening a EcoStruxure Control Expert project, you have the option to open the project in read-only mode. If this option is not selected and the project is still opening in read-only mode, follow the steps below
1. Close the project.
2. Locate the .stu project file on your computer
3. Right click on the project file and select properties
4. uncheck the "Read-only" attribute under the "General" tab of the file properties
5. Select "apply", then OK
6. Open the .stu project file in Control Expert and it should now open in Read/Write mode

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

  • Инструмент для подбора продукции

    Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

  • Получить коммерческое предложение

    Заполните заявку онлайн, и с вами свяжется наш эксперт.

  • Где купить?

    Легко находите ближайшего к вам дистрибьютора Schneider Electric.

  • Центр поддержки

    Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings