Do Vijeo Designer Events have an Active state?

Issue:
When setting the "Alarm & Event List" to Active for an Event Group, nothing is display during runtime when there are Events. The only settings that display Events are History and Log.

Product Line:
Vijeo Designer (all versions)

Resolution:
Events in Vijeo Designer have no concept of "state". In essence, an event is something that has occurred already in the past. Therefore is no such thing as an Active event in Vijeo Designer. When using the Alarm & Event summary, the setting "Alarm & Event List" can only be set to History or Log for Events. If monitoring states is required, it is recommended to use Alarms rather than Events.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings