How to clear the SD Card Error on the BMXNOE0100?
Issue:
I'm seeing the SD Card Error LED on solid on the BMXNOE0100. How can I clear this error?
Product Line:
M340
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
The likely cause of the SD Card Error was that the card was removed or inserted when the rack was powered up.
This error can be cleared by power cycling the rack or simply removing the BMXNOE0100 from the backplane and reseating it into its slot position.
In both cases, it will power up and get its configuration from the CPU module.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.