Чем мы можем помочь сегодня?

Where can I find instructions on installing the VW3A3600 Option Card Module on a compact version of the ATV320?

Issue:
How do I install the VW3A3600 on my ATV320?

Product Line:
Altivar 320 (compact version only)
VW3A3600 Option Card Module

Environment:
All models

Cause:
Installation Instructions

Resolution:
Installation instructions for the VW3A3600 Option Card Module (used only with the compact versions of the ATV320) can be found here, below, and are also attached.
option card

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Schneider Electric Казахстан

Узнайте больше

Линейка:

Узнайте больше

Линейка:

Нужна помощь?

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.