How do I set the deceleration time on a ATV320?

Issue:
Setting deceleration time on a ATV320.

Product Line:
ATV320

Resolution:
Parameters described in this page can be accessed by: DRI- > CONF > FULL > SIM
Goto Configuration Mode (ConF)  > Enter
Goto to FULL > Enter
Goto SIM > > Enter
Goto deC [Deceleration]  default  3.0s
Set desired value for deceleration time.