Can I assign or change digital input functions from the I/O menu in SoMove?
Resolution:
No. The Digital Inputs section in the I/O menu of SoMove is read‑only and is used for monitoring input assignments only.
To assign or change the function of a digital input, you must go to the specific function parameter you want to control (such as Stop, Forward/Reverse, Fault Reset, etc.) and then assign the desired digital input from within that function’s settings.
In other words, digital inputs are assigned from the function side, not from the I/O menu itself.