Чем мы можем помочь сегодня?
PME maintenance tasks fail with error 0x1F4 if IONMaintenance user is not added to the Administrators group
Issue
PME maintenance tasks fail with error 0x1F4 if IONMaintenance user is not added to the Administrators group
In the SQL Error logs, you may see the following error
"Login failed for user 'ServerName\IONMaintenance'. Reason: Failed to open the explicitly specified database 'ION_Network'. [CLIENT: <local machine>]"
Facts
- If IONMaintenance user is added to windows administrator group, the tasks run successfully
- IONMaintenance user roles are correctly set up in SQL for the 4 PME databases
- IONMaintenance user has full write access to the Backup destination folder
- IONMaintenance is a member of "Users" group
Product Line
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
PME Standalone systems
Cause
The privileges granted to the group BUILTIN\Users has higher priority over User privileges.
Resolution
In SQL, grant "db_backupoperator", "db_ddladmin" and "Maintenance" Membership for "BUILTIN\Users" for all PME databases
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Категория:
Узнайте больше
Категория:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.