What would be the recommended cable size for connecting a dynamic braking resistor?
Issue:
Are there recommended cable sizes for connecting a dynamic braking resistor?
Product Line:
Altivar 930
Environment:
All models and serial numbers
Cause:
NA
Resolution:
When sizing the cable to be connected between the drive and the braking resistor, it is simply a matter of taking the drive's Max DC bus voltage level and dividing it by the brake resistor value to determine the current through the resistor.
I(amps) = V(volts) / R(ohms)
The bus voltage divided by the ohm rating of the resistor will give you the maximum current draw. Also, when the circuit is very noisy, it is best to use shielded cable if you have noise concerns.
Are there recommended cable sizes for connecting a dynamic braking resistor?
Product Line:
Altivar 930
Environment:
All models and serial numbers
Cause:
NA
Resolution:
When sizing the cable to be connected between the drive and the braking resistor, it is simply a matter of taking the drive's Max DC bus voltage level and dividing it by the brake resistor value to determine the current through the resistor.
I(amps) = V(volts) / R(ohms)
The bus voltage divided by the ohm rating of the resistor will give you the maximum current draw. Also, when the circuit is very noisy, it is best to use shielded cable if you have noise concerns.
Опубликовано для: Schneider Electric Казахстан
Узнайте больше
Линейка:
Узнайте больше
Линейка:
Нужна помощь?
Инструмент для подбора продукции
Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.
Получить коммерческое предложение
Заполните заявку онлайн, и с вами свяжется наш эксперт.
Где купить?
Легко находите ближайшего к вам дистрибьютора Schneider Electric.
Центр поддержки
Находите ресурсы поддержки для всех ваших потребностей в одном месте.