Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
Unable to download to HMISTO7 over USB cable with Virtual Machine

Issue:
Download over USB cable fails to start when using a Virtual Machine (VMware, Fusion, etc) running EcoStruxure Operator Terminal Expert

Product Line:
HMISTO, HMIGTU, HMIST, EcoStruxure Operator Terminal Expert

Resolution:
When running EcoStruxure Operator Terminal Expert in a Virtual Machine (VMWare, Fusion, etc), ensure to set the USB Compatibility to version 1.1 if you require to download to the HMI via USB cable. If you leave it at 3.0 or 2.0, the USB download will not start.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings