How to Update the Application for the Vigilohm IMDLRDH
Note: Implementing a new application in your IMDLRDH will erase your previous configuration.

To update the the application program of your IMDLRDH you need to :
  1. Have a formatted USB key
  2. Download the latest version of the application : https://www.se.com/ww/en/download/document/MFR2858700_Ver_2.0.0/
  3. Unzip the content and place the extracted files on the root of your USB Key
  4. Switch off the IMDLRDH
  5. Plug the USB Key in the USB port of the IMDLRDH
  6. Power on the IMDLRDH
  7. Wait for the program to be uploaded in the IMDLRDH
  8. Remove the USB key once the program is uploaded
After these steps you need to perform the commissioning of your IMDLRDH.