Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
Adding an Ethernet module (BMXNOC040x, 140NOC78xxx ) causes Control Expert 15 to close.
Adding a BMXNOC040x or 140NOC78xxx to the applicable rack will return the following error message.  This will be followed by an unexpected closure of Control Expert 15.






This issue will occur if the module is added to a Control Expert application after installing the following hot fixes
  • 'ControlExpert_V150_HF0380584E'
  • ControlExpert_V150_HF_Integrity_Check'


This issue applies to the following DTM related modules::

M580 :
  • BMXNOC0402


M340 :
  • BMXNOC0401
  • BMXNOC0401.2


Quantum :
  • 140NOC78100,
  • 140NOC78100.2,
  • 140NOC78000,
  • 140NOC78000.2


The following steps can be used as a workaround,
  • Uninstall Control Expert.
  • Reinstall Control Expert.
  • Install all hot fixes except 'ControlExpert_V150_HF0380584E'.


This issue will be fixed in a soon to be released hot fix.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings