Galaxy RPP “Fingersafe IP2X” NQ Panelboards

Article available in these languages:

Issue:
The new Galaxy RPP has multiple panelboard options.  One of them is the IP2X Fingersafe panelboard which greatly restricts exposure to live parts.

These panelboards use the standard Square D QOB breakers but require some adapters to make them fit and increase safety.

Product line:
GRPPIP2X84, GRPPIP2X89

Environment:
All models, all serial numbers

Cause:
Electrocution is one of the top causes of construction injury.  The NQ panelboard reduces this risk by limiting exposure to live components.

Resolution:
To install standard Sq D QOB breakers into the Galaxy RPP with the NQ Panelboard, you will need an accessory jaw kit, and Fingersafe Barriers.

Parts:

Catalog NumberQuantity per packageDescription
QOFSBF1212NQ IP2X Bus Finger Filler *3
QOFSLALB1212NQ IP2X QO(B) Lug Cover Low Amp
QOFSHALB1212NQ IP2X QO(B) Lug Cover High Amp
QO1PJ1515QOB Jaw Kit4
QOBRT1QOB Breaker Removal Kit *4
*3 Used only with Standard IP2X design
*4 Used only with Enhanced IP2X design

Note:

IP2X finger-safe protection uses bus finger filler covers installed in empty breaker spaces, whereas Enhanced IP2X protection covers the bus itself, eliminating the need for breaker filler covers in unused spaces.


References:
https://www.se.com/us/en/product/GRPPIP2X84/galaxy-rpp-with-fingersafe-ip2x-panelboard-white/

https://download.schneider-electric.com/files?p_File_Name=998-20824083_GMA-US_Galaxy+RPP+brochure_HR_WEB.pdf&p_Doc_Ref=GalaxyRPP_Brochure_EN&p_enDocType=Catalog

https://download.schneider-electric.com/files?p_enDocType=Brochure&p_File_Name=1640BR1701_NQ_FingerSafe1-2019.pdf&p_Doc_Ref=1640BR1701

Schneider Electric Казахстан

Узнайте больше

Изделие:

Линейка:

Узнайте больше

Изделие:

Линейка:

Нужна помощь?

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.