Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
EcoStruxure Automation Expert [21.1]:How to resolve the issue "Deploy Plugin AvevaServerPlugin not installed" ?

This knowledge base helps the user to resolve the "Deploy Plugin AvevaServerPlugin not installed" issue that comes under the Deploy and diagnostic tab when the AVEVA_SERVER device is being used in the project?
The error message shows as below highlighted in Yellow color
issue

The issue is happening as the mandatory plugin required for AVEVA_SERVER device is not installed in the machine.

The AvevaServerPlugin can be installed  either by reinstall/repair the Ecostruxure Automation Expert

The user needs to select the "AutoBuild AVEVA InTouch OMI" for any of the highlighted selections and complete the installation procedure.
NOTE: The Default selection is "This Feature will not be available".Hence plugin is not getting installed by default.
solution

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings