BMEAHI0812 FDR Server shows offline
Issue
Transfer to FDR server shows offline
Product Line
BMEAHI0812
BMEAHO0412
Environment
EcoStruxure Control Expert
Resolution
There can be a couple of reasons that the FDR server shows offline. One, you must have an Ethernet connection. You cannot use the USB connection. Another reason could be that the FTP service in security has been disabled. FTP needs to be enabled.