Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
What is the function of PLC input ON/OFF on TeSys Giga contactor ?
Normally the contactor operation is controlled by AC or DC control voltage input to A1-A2terminals. But in advanced version contactor, the contactor can be controlled by additional 24V DC PLC inputs to X1-X2-X3 terminals.

When the PLC switch is ON, the contactor function is controlled by PLC input.
When the PLC switch is OFF, the contactor is controlled by control voltage input to A1-A2.


image.png

The electrical schematic and function description are available on the installation guide DOCA0189EN and here is the link:TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings