Ecostruxure Automation Expert 21.1: How to import images on to the Canvas
This document explains on How to import images to the Canvas of Ecostruxure Automation Expert Software.

Currently there is no direct option to import images on to Canvas page, so the below procedure helps user to import Images on to the Canvas page.

1. Go to the respective Canvas page where user wants to import an image and draw a rectangle of required size, as shown below

p1

2. At right side, in the Properties of Rectangle, select the Image option and navigate to the required image file, then click on Open.

p2

3. The Image will be imposed on to the complete area of Rectangle, then you can resize the image as per your requirement.

p3

This document is applicable for all current versions of Ecostruxure Automation Expert.