Чем мы можем помочь сегодня?

Unable to install PLC-USB driver due to user conflict

Installing the 'SchneiderPLCUSBDriverSuite V14.15.0.0' returns the following error.:
PLCUSB Driver

Use the following steps to run the ps1 file named 'Release-PerUserDrivers.ps1' can be used to resolve the issue.

  • Browse to the location you stored the ps1-file in File Explorer and choose; File-> Open Windows PowerShell.
  • Type (part of) the name of the script.
  • Press TAB to auto complete then name. Note: Do this even when you typed the name in full. ...
  • Press ENTER to execute the script.
Note: This doesn’t uninstall the old driver versions, but it deletes any 'SchneiderPLCUSBDriverSuite' installer related
registry keys that causes Windows to detect and refuse the install/uninstall of the driver components..

Schneider Electric Казахстан

Вложения
Release-PerUserDrivers.ps1.txt [16.07 KB]
Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings