Power SCADA Operation (2020/2021) with OPCUA Driver v4.00.05.00000: OPCUA client not working for tags include Chinese characters

Issue
One issue related to PSO2020+CU1 as OPCUA client issue. with the newest OPC driver - OPCUA Driver v4.00.05.00000.
If the OPCUA server tags include Chinese characters, PSO can’t read the data and it will show bad.

We have replicated customer’s issue.
OPC1
OPC2
Also test with other OPC UA client and it can be read.
OPC3

Environment
Power SCADA Operation (PSO) 2020 R2
EcoStruxure Power Operation (EPO) 2021
KEPServerEX 6
Matrikon OPC UA Explorer

Cause
Citect does not support Unicode tag address. It also does not support Unicode tag values, tag names, etc.

Resolution
For tag address/name you can only use standard ASCII characters (no special characters).

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:

Нужна помощь?

Нужна помощь?

Инструмент для подбора продукции

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings