Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
Why PLC Simulator can’t receive external communication ?
Since Control Expert V15.0, a new option has been introduced on PLC Simulator: the listening IP address. The default value is now 127.0.0.1.
This value is used to avoid that the PLC Simulator could be reached from external IP port. This is a mitigation to avoid cybersecurity attack.
Nevertheless, If the user wants the PLC Simulator listening all the IP port you need to set this listening IP to 0.0.0.0 as it was in the previous version or assigned the IP address of its PC External port.

Go to option of the PLC Simulator and change the Listening IP Address from 127.0.0.1 to 0.0.0.0 like below:

PLC Simulator Option

PLC Simulator Listening IP port

And then restart PLC Simulator.

Product Line
Control Expert CE v15.0 and above
PLC Simulator

Environment

Windows

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings