How do you set up Brake Logic Control on a ATV930 drive?

Issue:

Setting up Brake Logic Control on a ATV930 drive.

Product Line:

ATV930

Environment:

Brake Logic Control

Cause:

n/a

Resolution:

Go to 5.9 menu (Hoisting Functions)

Brake Logic Control- set to R2

Movement type- Hoisting or Traveling

Brake Contact- set to the corresponding Digital input

Brake Relay Feedback- set to the corresponding Digital input

Brake release Pulse – set to yes or no or 2IBR

Brake release Current-current you want the brake to release

Brake Release Time- suggest around .5 secs

Brake release Freq- Auto

Brake engage freq-Auto

Brake engage delay-.00 secs

Brake engage time-time to engage the brake- suggest around .5 secs

Engage at reversal- No (if you do not want the brakes to engage in reverse)

Jump at reversal-auto

Time to rstart-.00 secs

Current ramp time-.00 sec

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:

Нужна помощь?

Нужна помощь?

Инструмент для подбора продукции

Инструмент для подбора продукции

Быстро и легко находите подходящие продукты и принадлежности для ваших условий применения.

Получить коммерческое предложение

Получить коммерческое предложение

Заполните заявку онлайн, и с вами свяжется наш эксперт.

Где купить?

Где купить?

Легко находите ближайшего к вам дистрибьютора Schneider Electric.

Центр поддержки

Центр поддержки

Находите ресурсы поддержки для всех ваших потребностей в одном месте.

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings