Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
NetBotz camera motion detection stops working after firmware upgrade.
Issue:
NetBotz camera motion detection stops working after upgrade.

Product Line:
NetBotz

Environment:
NBRK0750, NBWL0755, NBPD0165

Cause:
Some instances have been seen where after an upgrade to the NetBotz appliance, a motion mask is applied to the entire camera image which causes motion detection events / clips to stop.


Resolution:

Within the NetBotz appliance user interface, set a small section of motion mask and save it. Then go back and clear the motion mask for that camera, this should reset the cameras motion mask to a default state. You will need to do this for each camera which is not reporting motion events / clips.
*If you require to have a section of the camera with a motion mask, you will need to set that up after this reset motion mask procedure is complete.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings