Issue:
What is the BACnet unit load and Transceiver specs for ATV212 Drive?
Product Line:
ATV212, Altivar 212
Environment:
All
Cause:
NA
Resolution:
Below complete data for ATV212 BACnet:
Transceiver Type
- RS485 Transceiver Fail Safe or non-failsafe ? RS485 Transceiver Fail Safe on ATV212.
Transceiver Load
1) What is your unit load ? 32 unit load can be placed on the bus.
2) What is your transceiver load ? 1 unit load.
3) What is your local bias load ? In ATV212 circuit, no bias resistor, but we have a termination of 120 Ohm managed by switch SW103.
What is the BACnet unit load and Transceiver specs for ATV212 Drive?
Product Line:
ATV212, Altivar 212
Environment:
All
Cause:
NA
Resolution:
Below complete data for ATV212 BACnet:
Transceiver Type
- RS485 Transceiver Fail Safe or non-failsafe ? RS485 Transceiver Fail Safe on ATV212.
Transceiver Load
1) What is your unit load ? 32 unit load can be placed on the bus.
2) What is your transceiver load ? 1 unit load.
3) What is your local bias load ? In ATV212 circuit, no bias resistor, but we have a termination of 120 Ohm managed by switch SW103.
Опубликовано для:Schneider Electric Казахстан



