In EcoStruxure Power Commission, sometimes while generating the QR code you might get error message "Unable to authenticate the cloud services. Please contact CCC to report the issue" as given in screen shot below:

Unable to authenticate


When you face such issues, you can follow the below steps to ensure you are not blocked. You need to make a parameter "false" in the configuration file as mentioned in below steps.

Steps to unblock:

1) Save all your projects and Close EPC (Very important step)
2) Check and confirm whether DigiCert Global Root CA certificate is available in the system. For that please follow below steps:
  1. Press Windows+R  -> Then type certmgr.msc and click on OK
  2. Certificate manager console will be opening and check whether the certificate is installed as mentioned in the below screenshot:
Certificate

If you do not have certificate, please contact Schneider Electric Country Customer Care team
If you have the above certificate please follow the next steps to recover from the error.


3) Navigate to path:
C:\Program Files (x86)\Schneider Electric\Ecoreach V2\Package\Server
4) Find the file "EcoreachCore.exe.config"
5) Right click on this file and click "Edit" with notepad or notepad++
6) Change the following data(by default it will be "true", we are changing to false) :
<add key="ValidateCertificate" value="false" />
7) Save the file and close the file
8) Relaunch EPC application and try to generate QR code

These above steps should unblock you and if you still face any issues, please contact your country customer support team.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings