Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
How to Modify RemoteConnect Objects Associated with Logic Variables Online

Typically, if a user wants to manipulate variables in a logic program using RemoteConnect, they can manipulate these in an Animation table. When using SCADApack x70 devices, this statement is true only for elementary variables or internal DDT type variables. A user cannot manipulate variables that are of the type "T_SPx70_XXX"

See logic example below with an animation table in the Logic Editor. In this example, if a user was to try and manipulate the "Start" variable to start the motor, it cannot be accessed via the Animation table. It also cannot be manipulated by right-clicking on the "Start" variable to change the state in the drop-down menu of the ladder section.

animationlogic

The way to manipulate the "T_SPx70_XXX" objects associated with variables is to use the Object Browsers in RemoteConnect. Please see the example Browser in RemoteConnect below.

browser

Further information about Object browsers, T_SPx70 variables and working online with SCADAPack x70 devices can be found in the RemoteConnect help manuals installed with RemoteConnect

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings