Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
How to connect my Control Expert client to the server ?

Before starting Control Expert Topology Manager (TM) on the client side, please follow these steps:

  1. Close TM on the server side.
  2. Open the Server Configuration.
  3. In the Listening Connections tab, update the Listening IP address:
    • Either select the Ethernet card used to communicate with the client PC,
    • Or enter 0.0.0.0 to listen on all Ethernet interfaces.

Server Configuration listenning IP address

4- Apply the changes and close the configuration tool.
5- On the client side, open TM and go to User Preferences.
6- In the Networks and Servers tab, update the Control Expert Server Address with the correct IP and port:
  • For example: IP = 192.168.189.1, Port = 19950.

User Preferences define IP address of TM server

7- Close and relaunch TM on the client side.

You should now be able to connect to the server successfully.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings