Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
How can I upgrade my SCADAPack x70 devices' Realflo licence?
  • Contact your Local Representative and purchase the required upgrade license.
  • Our customer support team will e-mail you with the upgrade License that was purchased.
  • Saved this License in your desktop folder.
  • Create a new project using RemoteConnect.
  • Go online with the device.
  • Under My Network, right-click on SCADAPack x70 Controller Settings -DeviceDTM and select Additional Functions > Apply License to Device
Apply License
  • in the Apply License to Device dialog, click Browse to navigate to the location where the license file is stored. The license file has a .lic extension.
  • In the open dialog, select the license file, then click Open
  • In the Apply License to Device dialog, click Ok. A restart of the device is required to activate license options after the license has been successfully applied to it.
  • In the pop-up dialog, click Yes to confirm.
apply license 2
  • Verify the license's modifications. Under Online Diags>Licensing then hit refresh button.
apply license 3

Schneider Electric Казахстан

Узнайте больше
Изделие:
Узнайте больше
Изделие:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings