How can I upgrade my SCADAPack x70 devices' Realflo Licence?

  • Contact your Local Representative and purchase the required upgrade license.
  • Our customer support team will e-mail you with the upgrade license that was purchased.
  • Saved this license in your desktop folder.
  • Create a new project using RemoteConnect.
  • Go online with the device.
  • Under My Network, right-click on SCADAPack x70 Controller Settings -DeviceDTM and select Additional Functions > Apply License to Device

Apply License

  • in the Apply License to Device dialog, click Browse to navigate to the location where the license file is stored. The license file has a .lic extension.
  • In the open dialog, select the license file, then click Open
  • In the Apply License to Device dialog, click Ok. A restart of the device is required to activate license options after the license has been successfully applied to it.
  • In the pop-up dialog, click Yes to confirm.

apply license 2

  • Verify the license's modifications. Under Online Diags>Licensing then hit refresh button.

apply license 3