Чем мы можем помочь сегодня?

How Can I select Gateway/Bridge Device option in IOSCANNING for M580 CPU ?

Issue:

How Can I select Gateway/Bridge Device option in IOSCANNING for M580 CPU ?

Product Line:

M580

Environment:

EcoStruxure Control Expert

Resolution:

User needs to install EcoStruxure Control Expert 15.1 or higher version and choose the CPU version as SV3.20 or higher in hardware configuration .

2.JPG

Select the check box to enable this feature. The communication module doubles the timeout setting by increasing the number of re-transmissions to 6 (instead of the typical setting of 3).

1.JPG

Here is one demo wireshark trace when M580 reset the TCP connection after 6 times TCP retransmissions without receiving the response of ModbusTCP server device after Gateway/Bridge Device option is selected.

3.JPG

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка:
  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings