Наши бренды

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
		
Чем мы можем помочь сегодня?
NetBotz camera pod NBPD0165 occasionally changes to black & white image in well lit room.
Issue:
NetBotz camera pod NBPD0165 occasionally changes to black & white image when in a well lit room.

Product Line:
NetBotz

Environment:
NBPD0165 camera pod

Cause:
The NetBotz 165 camera pod has both day and night capabilities. When in night mode / dark mode, the image changes to black and white.
There are occasions where the image will change to black & white during the day or when in a well lit room.

Resolution:
Please log on to the camera directly.

Find the setting under "IR Function" for "Day/Night Threshold".

Change night to day setting from 7 to 4 as per the following image.

Camera Menu

Schneider Electric Казахстан

  • Документация по продукту
  • Загрузка ПО
  • Система подбора продукции
  • Замена продукта
  • Центр справки и связи
  • Найти наши офисы
  • Получить коммерческое предложение
  • Где купить
  • Сообщество Schneider Electric
  • Карьера
  • Сведения о компании
  • Сообщить о нарушении
  • Доступность
  • Отдел новостей
  • Инвесторы
  • EcoStruxure
  • Поиск вакансий
  • Блог
  • Политика конфиденциальности
  • Уведомление об использовании файлов cookie
  • Change your cookie settings